Application
Contamination control and condition monitoring of liquid fuel
Standards and methods
ISO 11171 | ISO 4402 | ISO 4406 | SAE AS4059 |
Sample input
Pressure range: 0 to 6 bar
Sample flow rate: 25 ml/min
Volumetric particle sensor PAMAS HX
Calibration range: 4 to 70 µm(c) as per calibration standard ISO 11171
Measurement in eight size channels: > 4 µm(c), > 6 µm(c), > 10 µm(c), > 14 µm(c), > 21 µm(c), > 25 µm(c), > 38 µm(c) and > 70 µm(c)
Maximum particle concentration: 24.000 particles per ml at a coincidence quote of 7.8% and a flow rate of 25 ml/min
Standardised measuring results
Report of measuring results according to cleanliness class standards SAE AS 4059 and ISO 4406.
The particle counter measures ISO classes from 0 to 22.
Interfaces for data transfer
Standard equipment: RS485
Optional equipment: analogue 4-20 mA interface. Parallel data transmission for the size channels > 4, > 6, > 14 and > 70 µm(c) or serial data transmission for all eight size channels.
Software
PAMAS POV (PAMAS Online Visualisation): Software for online visualisation of measuring results and for long-term trend monitoring